PVC Insulated Nylon Sheathed Cable
Type and temperature rating
TYPE |
THHN |
THWN |
THWN-2 |
TFN |
TFFN |
Temperature rating |
90℃Dry |
75℃Dry or Wet |
90℃Dry or Wet |
90℃Dry or Wet |
90℃Dry or Wet |
Description of the purpose and usage properties
The nylon sheathed cable has more excellences in physical and electrical performance than the PVC cable.
The cable has smaller outer diameter, lighter weight, less static friction coefficient than the same size of PVC cable, which greatly improve safety and convenience in installation and assembly of the cable.
It is self-lubrication, and has good resistance to corrosion, oil, acids, alkali, and moisture.
The cable is widely used in fixed installation, home appliance, lighting equipment, construction and aviation engine room with voltage up to 450/750V.
Its permitted long term working temperature shall be 70℃ or 90℃, installation temperature shall be over 0℃, and maximum bending radius shall be not less than 4 times of outer diameter of the cable.
Standard
UL83 UL66
Specification and construction (mm)
型號規格 |
導體根數 |
單線直徑mm |
絕緣厚度mm |
尼龍厚度mm |
參考外徑mm |
參考重量kg/km |
15℃絕緣電阻GΩ.m |
18AWG |
7 |
0.39 |
0.38 |
0.1 |
2.20 |
11.8 |
|
16AWG |
7 |
0.49 |
0.38 |
0.1 |
2.50 |
17 |
|
14AWG |
1 |
1.63 |
0.38 |
0.1 |
2.60 |
25 |
205 |
12AWG |
1 |
2.05 |
0.38 |
0.1 |
3.10 |
36.9 |
175 |
10AWG |
1 |
2.59 |
0.51 |
0.1 |
3.90 |
59 |
180 |
8AWG |
7 |
1.23 |
0.76 |
0.13 |
5.50 |
98 |
185 |
6AWG |
7 |
1.56 |
0.76 |
0.16 |
6.60 |
151 |
155 |
4AWG |
7 |
1.96 |
1.02 |
0.15 |
8.30 |
240 |
155 |
3AWG |
7 |
2.2 |
1.02 |
0.15 |
8.90 |
294 |
145 |
2AWG |
7 |
2.47 |
1.02 |
0.15 |
9.80 |
364 |
130 |
1AWG |
19 |
1.69 |
1.27 |
0.18 |
11.40 |
470 |
140 |
1/0AWG |
19 |
1.89 |
1.27 |
0.18 |
12.40 |
577 |
130 |
2/0AWG |
19 |
2.12 |
1.27 |
0.18 |
13.60 |
714 |
115 |
3/0AWG |
19 |
2.39 |
1.27 |
0.18 |
14.90 |
893 |
105 |
4/0AWG |
19 |
2.68 |
1.27 |
0.18 |
16.40 |
1109 |
95 |
250MCM |
37 |
2.09 |
1.52 |
0.2 |
18.10 |
1326 |
105 |
300kcmil |
37 |
2.29 |
1.52 |
0.2 |
19.50 |
176 |
95 |
350kmcil |
37 |
2.47 |
1.52 |
0.2 |
20.80 |
1820 |
90 |
400kcmil |
37 |
2.64 |
1.52 |
0.2 |
22.10 |
2066 |
80 |
450kcmil |
37 |
2.8 |
1.52 |
0.2 |
23.10 |
2312 |
80 |
500kcmil |
37 |
2.95 |
1.52 |
0.2 |
24.20 |
2555 |
75 |
550kcmil |
61 |
2.41 |
1.78 |
0.23 |
25.80 |
2837 |
80 |
600kcmil |
61 |
2.52 |
1.78 |
0.23 |
26.80 |
3090 |
80 |
650kcmil |
61 |
2.62 |
1.78 |
0.23 |
27.80 |
3329 |
75 |
700kcmil |
61 |
2.72 |
1.78 |
0.23 |
28.70 |
3577 |
70 |
750kcmil |
61 |
2.82 |
1.78 |
0.23 |
29.50 |
3834 |
70 |
800kcmil |
61 |
2.91 |
1.78 |
0.23 |
30.40 |
4073 |
70 |
900kcmil |
61 |
3.09 |
1.78 |
0.23 |
32.00 |
4573 |
65 |
1000kcmil |
61 |
3.25 |
1.78 |
0.23 |
33.50 |
5042 |
60 |
Main technical performance
Test Item |
Test Requirement |
Test Result |
Test Standard |
Flame test |
Pass |
Pass |
UL 1581 |
Insulation resistance in water |
Pass |
Pass |
UL 1581 |
Convolute and cold bend test |
No cracks |
No cracks |
UL 1581 |
Oil resistance test |
Pass |
Pass |
UL 1581 |
Delivery
The cable shall be delivered in coil. Each package of delivery shall be 100 meters, among which can include the short wires of no less than 10 meters, and the length of the short wires shall not be over 10% of total length of each package.
Any delivery length shall be permitted in accordance with the purchasers' requirement
付款方式︰ TT